Homes & switchboards
For homeowners concerned about an ageing switchboard, recurring trips, discolouration or changes in how a circuit is operating.
Electrical & solar inspections
Find unusual heat in your switchboard or solar system, understand what is causing it, and get clear advice on what to do next.
Solair Electrical combines thermal imaging with visual inspection and appropriate electrical testing. We investigate concerns, document our findings and explain any repairs or further checks your installation needs.
Tell us your suburb and whether you need a switchboard, solar or combined inspection.
Read our reviews
A closer look at electrical condition
Unusual heat can help direct an investigation before a problem becomes obvious from the outside. A thermal inspection is useful when you have a specific concern or want a clearer picture of the condition of accessible equipment.
For homeowners concerned about an ageing switchboard, recurring trips, discolouration or changes in how a circuit is operating.
For systems with reduced output, suspected panel damage or concerns after hail. Thermal images help us identify areas that need closer investigation.
For owners and managers who need documented findings and a practical plan for electrical maintenance or follow-up work.
Do not open a switchboard, touch damaged equipment or climb onto the roof to investigate. Keep clear and call for advice. A routine thermal inspection is not an emergency response service.
Two areas. One practical approach.
We agree the scope with you before the visit. Access, equipment condition, operating load and weather can affect what can be inspected and how useful the images will be.
We look for unusual temperature patterns in accessible equipment and compare them with the installation’s condition and operating load.
A hot connection may need further investigation. Thermal imaging alone cannot establish the cause or prove that the rest of the installation is safe.
If rectification is needed, we can discuss repairs or a switchboard upgrade.
We assess accessible solar panels and relevant system components for thermal patterns that warrant investigation, supported by visual checks and electrical testing.
Sunlight, shading, wind, reflections and system operation all affect the image. We interpret what we see in context rather than treating every bright area as a fault.
For a broader system condition check, see our solar inspection service.
More than a thermal photograph
A thermal camera shows surface temperature patterns. It helps us decide where to look more closely, but it cannot see through every enclosure or identify every electrical fault.
We combine images with visual findings, the equipment’s operating conditions and suitable electrical tests. This gives you a more useful explanation of the issue and the next step.
We explain any inspection limitations in the findings rather than overstating what the image shows.
What to expect
Let us know the property location, equipment involved and any symptoms or recent storm damage. We confirm the proposed scope, access requirements and quote.
We carry out the agreed visual checks, thermal imaging and appropriate testing. Where safe operation or conditions limit the inspection, we explain what could not be assessed.
We explain what we found, the supporting evidence and the recommended action. If an immediate hazard is identified, making the affected equipment safe takes priority.
You receive the agreed inspection documentation and practical next steps. Any further testing, repairs or replacement work is discussed with you.
Real work by Solair Electrical
These examples show how thermal imaging supports an investigation. Findings come from the overall inspection and testing, not the colours in a thermal image alone.
Switchboard example
Thermal imaging highlighted heat at the main switch and hot water circuit breaker. Further investigation identified loose connections.
The old devices were replaced, and the whole house was tested as part of a safety check, with a report provided to the customer.
The useful outcome: the customer received an explanation of the faults, rectification and a documented safety check rather than just a thermal photograph.


Solar inspection example
On hail-damaged solar systems inspected by Solair, thermal imaging showed localised hot spots that needed closer assessment. Inspection and testing informed the recommendations for damaged panels and replacement systems.
The daylight photograph shows visible panel damage. It is a separate example and is not presented as a matched view of the thermal image above.
For an assessment intended to support a claim, see our solar insurance inspection report service.

Customer case
In one solar inspection, thermal imaging and short-circuit testing identified failed panels that posed a fire hazard. The affected system was immediately isolated, the broken panels were removed and a report was provided to the customer.
In that case, the insurer approved the claim within two weeks and a new system was installed the following week.
This is one customer’s outcome, not a promise of approval or timing. Insurance decisions and installation schedules vary.

Tell us what you have noticed. We can discuss whether thermal imaging is suitable and what inspection scope makes sense for your property.
Useful evidence, clearly explained
Your agreed report brings the inspection findings together, with supporting photographs and recommendations relevant to the work carried out.
For solar insurance matters, confirm your insurer’s requirements before booking. The insurer makes its own decision about cover and the evidence it needs.
A privacy-edited example showing how solar inspection findings can be documented. Customer-identifying information has been removed.
This is a solar report example, not a switchboard report or a guarantee that every inspection will have the same scope.
View sample reportPDF · 5 pages · approximately 6 MB
Common questions
No. It shows surface temperature patterns under the conditions present at the time. Hidden components, low loads and intermittent faults can limit what is visible. We use it alongside other inspection methods and testing.
No. Normal operation, different loads, reflections and environmental conditions can create temperature differences. We investigate unusual patterns and interpret them alongside the equipment’s condition and test results.
Some thermal observations need equipment to be operating, while other checks or repairs may require isolation. We discuss access and any expected interruption with you. Safe work requirements determine how the inspection proceeds.
Yes, we can assess the system within an agreed scope. Visible damage, thermal findings and suitable testing may all be relevant. Thermal imaging alone does not establish the cause of damage. If you need documentation for a claim, ask about our solar insurance inspection report service.
We explain the concern and take appropriate steps to make the affected equipment safe. Depending on the issue, this may involve isolation and further repair or replacement work. We discuss the recommended next steps with you.
The quote depends on the equipment, access, inspection scope, testing and reporting required. Send us your location and a short description of the job so we can confirm the appropriate scope and pricing.
Your suburb, whether the concern involves solar or a switchboard, and a description of any symptoms. If you already have photographs or inverter messages, let us know. Do not remove covers or access the roof to take photographs.
We service Brisbane, Redlands and surrounding areas. Include your suburb when you contact us so we can confirm availability for your location and the work you need.
Brisbane · Redlands · Surrounding areas
Get a clearer understanding of your installation, with practical findings and straightforward advice from Solair Electrical.